Wavetek 147 Specifiche Pagina 364

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 363
Application Notes: Proofing and Testing
340
A
Terminal Isolation [76.605(a)(9)]
Terminal isolation shall be at least 18 dB. In reality, its usually much better
than this. Depending on the source of the purchase!
Ground Loops & Voltage Potential Differences
Use a device called a 188A to test for dangerous voltage potentials before
touching anything.
You could also use a voltmeter in the ammeter mode. Connect one lead to
the cable sheath/connector and another lead to a known good ground. If
current is flowing, there is an obvious voltage potential difference. You may
want to establish a ground before disconnecting the only ground you have
going. Call the electric company if the ground is in question.
Common bonding is required for the elimination of ground loops, but if the
power ground becomes dislodged a more serious problem could occur. If the
power company entrance into the house becomes disconnected from
corrosion or whatever, the house powering will use the cable grounding as
its neutral. Eventually the dielectric will melt.
Assure the house is grounded and bonded correctly for safety and
elimination of ground loops, which can cause hum related problems and
impulse burst noise.
To eliminate hum bars, try common mode coiling, ghost busters, or drop
isolators. Drop isolators have capacitors installed to block the voltage from
traveling on the sheath or center conductor while still allowing RF to pass.
We could also use common mode coiling, which is used to eliminate
common mode currents from entering through a breach in the cable sheath.
Take 10 feet of cable and coil into 7 turns approximately 5-6 inches in
diameter. If impulse noise or hum gets in at the TV tuner or from the power
ground, it will travel on the cable braiding until it dissipates or is induced onto
the center conductor. Coiling the drop cable prior to insertion into the house
appliance will "choke" out this reverse ingress before it finds that breach.
SigVision also makes a snap-on ferrite bead to attach to the coax, which will
impede common mode currents. One way to make a drop isolator would be
to connect two 75/300 ohm transformers back-to-back. This may be good for
troubleshooting, but may not conform to bonding ordinances and will cause
signal loss and leakage.
Hum [76.605(a)(10)]
Acterna equipment can measure hum on an unscrambled, active channel.
This is a peak-to-peak measurement. The definition of FCC hum is any low
frequency disturbance (< 1 kHz) and must be < 3%. This is usually caused
Vedere la pagina 363
1 2 ... 359 360 361 362 363 364 365 366 367 368 369 ... 409 410

Commenti su questo manuale

Nessun commento